THIS IS AN ACTUAL REPORT
SUBMITTED AFTER AN INSPECTION OF AN UNDISCLOSED PROPERTY.
The purpose of the investigation was to
observe, qualify, and record various defects, cracks, and
misalignment occurring in the structure pursuant to an analysis
of the cause.
Items have been documented that may need to
be corrected, changed, or are possibly out of code, or items
that should be brought up to minimum standards set forth by the
construction industry.
A.
DESCRIPTION
House is a one story four sided brick veneer home with an
addition that is sided with double six type vinyl siding. A
small portion of the exterior on the extreme right back of house
is stone veneer. There is an approximately 3’ walled patio in
front. There is no garage or carport. The roof is of three tab
shingles. There is also a finished basement. The house sits
approximately level with the street and the front yard is fairly
level. Starting at the front edge of the house, the yard begins
a rather sharp slope to the rear of the property. There is one
notable tree in the front yard that should it fall could strike
the house and cause damage.
B.
EXTERIOR
1.
Shingles on roof show signs of poor ventilation in attic.
2.
There are more than two sets of shingles on roof of main
portion of house. Addition portion of house has only one roof.
3.
Brick veneer and brick wall around front patio do not
have weep holes as required. (Brickwork predates code requiring
this.) This could lead to moisture damage between brick veneer
and structure.
4.
A/C condenser is out of level. This could void any
warranties on this unit.
5.
Tree from right side neighbors yard is leaning
precariously over fence and into yard approximately 15 feet.
This could cause damage to fence and present a safety hazard if
the tree should fall.
6.
Gable on right side of house is missing a louver. Also,
the molding attaching this gable to soffit on rear elevation of
roof is missing in addition to molding on front of same soffit
on the rear elevation.
7.
Stair stringers on deck are making contact with ground.
They are not rated for ground contact.
8.
Deck is incorrectly nailed to 2x2 ledger.
9.
Deck is built on framed walls that create an enclosure
such as a storage room. This room appears to retain a good deal
of moisture, as there is a fair quantity of white mold forming
on deck joists.
10.
Left side of house has masonry fireplace that is covered
with real stucco.
11.
Vegetation is growing in direct contact with back of
house. This can lead to termite and other insect infestation. No
evidence of such infestation was observed at the time of
inspection.
C.
INTERIOR
1.
Living room front hall and two bedrooms off this hall all
have Berber carpeting.
2.
Kitchen and sunroom areas have commercial indoor/outdoor
carpet.
3.
Kitchen has G.E. side-by-side refrigerator w/icemaker, A
Kenmore freestanding range and a Kenmore dishwasher. (Was not
able to inspect dishwasher for operation as it has digital
controls.) Range hood is a front vent type Made by Nutone.
4.
P-Trap for kitchen sink is not located in the under sink
cabinet. It is located under the floor level.
5.
Master bath located adjacent to the kitchen also has
P-trap below floor level.
6.
Outlet located directly behind toilet in same master bath
is not GFCI protected.
7.
Bathtub in hall bathroom does not have sealed fixtures.
This can allow water to seep behind wall and cause damage.
8.
Left rear master bath has pedestal sink. It also has
closet that requires globe over exposed light fixture, as this
is a fire hazard.
9.
There is cracking and bowing in the ceiling plaster in
the area leading from front room to the dining area.
10.
Hallway has louvered attic fan.
11.
Spiral staircase running from dining area has large gap
that a small child could easily fall through.
12.
Basement living area has a masonry fireplace.
13.
Large walk-in closet in basement area has non-GFCI
electrical strip within the 6’ safety area, however it does
not have power running to it at time of inspection.
14.
There is evidence of water damage on ceiling in basement
area adjacent to sliding glass doors. Tested for moisture and
found it to be currently wet.
15.
GFCI outlet in basement hallway is incorrectly wired with
open ground. It does not switch off when tested.
16.
Lower level of house does not have a smoke detector. This
is required as lower level contains a bedroom.
D.
ATTIC
1.
Attic insulation is not R-30 as required. (This house
predates R-30 requirement and is currently R-19.)
2.
Roof is stick built type.
3.
Attic fan mentioned in section C-10 does not have fire
switch. This presents a fire hazard.
4.
Junction box running to same fan does not have cover.
Electrical wire running to this box and to the fan is not in
protective conduit.
E.
ELECTRICAL
1.
Home has 200-amp electrical service.
2.
Panel box contains only one AFCI breaker however, when
tested, none of the four bedrooms required to have AFCI
protection show any result of power being disconnected to them
either to outlets or lighting. This constitutes a fire hazard.
3.
Enclosed area under the sunroom has two junction boxes
that have no covers and have exposed live wires. This is a
safety hazard.
F.
HEATING/AIR
1.
Furnace does not have any identifying label as to what
make or model it is.
2.
Gas line to furnace does not have drip leg. This can lead
to carbon- monoxide leakage into living area.
3.
There is no disconnecting switch on electrical line
leading to furnace.
G.
HOT WATER HEATER
1.
Water heater is a Hotpoint 40 Gallon model.
2.
H&P valve is not connected to drain pipe leading to
exterior of house as required.
This
report is not technically exhaustive nor is it likely to contain
every potential problem with this house. Some problems can be
hidden, but most leave signs of their presence. Our inspection
is thorough, but time and financial constraints limit the extent
of analysis.
Our goal
is to identify defects within the home. We define defects as any
items or portions of the property that are not in good working
order and repair (normal wear and tear accepted), or are in a
condition, which represents a significant risk of injury or
damage to persons or property.
The
listing does not contain every possible defect. Most items can
be repaired in a number of ways. It is assumed all repairs will
be done in a professional manner.
ATLANTA HOME
INSPECTION REPORT
REPORT SUBMITTED
WILLIAM DOUGLASS
HOME INSPECTOR
_______________________________
William Douglass